8625-2 Standard - 23
english
6.6.3
MODE
- setting the setpoint mode
Internal
setpoint
external
setpoint
Î Select here wheter the device shall work with internal or
external setpoint. The choice
External Setpoint
is shown by
the number 1 in the lower display line
(factory setting: external setpoint)
1
Fig.: Setting the setpoint mode
Setting the setpoint: internal setpoint
With internal setpoint setting, the setpoint value for the temperature is entered in
the previously set unit (°C or °F) and stored. The device controls to this value.
Settings are possible between -50 °C and 150 °C or -58 °F and 302 °F.
If it is attempted to set a value outside this range, the display will jump automatically
to 0 and a value must be entered within the range.
The unit corresponds to the value set in the menu item UNIT.
(Factory setting: 0.0).
increase digit
next digit
2 s
change sign at 4th place from
right
Fig.: Setting the setpoint: internal setpoint