Operating InstructionsType 8681 Control Head

Strany 2

10Basic Safety InstructionsBASIC SAFETY INSTRUCTIONS3. These safety instructions do not make allowance for any contingencies and events which may aris

Strany 3 - In h a l t

11Basic Safety InstructionsNOTE! Connection of the Control HeadDo not connect any mechanically rigid connection parts, in particular those with long l

Strany 4

12Basic Safety InstructionsGENERAL INFORMATION4. Contact address4.1. Bürkert Fluid Control Systems Sales Center Christian-Bürkert-Straße 13-17 D-74653

Strany 5

13System DescriptionSYSTEM DESCRIPTION5. Intended Application Area5.1. The Control Head Type 8681 has been designed for use as actuation of pneumatica

Strany 6

14System Descriptionshort mechanical and pneumatic installation times.•For increased safety requirements (e.g. in the explosion-risk area) a seal or

Strany 7

15System Description5.4.2. Fluid diagramControl Head Type 8681 - Fluid diagram (with restriction capability for each solenoid valve):Model with three

Strany 8 - OPERATING INSTRUCTIONS1

16System DescriptionNumber of solenoid valves5.4.3. The control head for process valves has been designed for single-acting and double-acting valve ac

Strany 9 - AUTHORIZED USE2

17System DescriptionPosition Measuring System5.4.6. The switching positions of the process valves are reported to the higher-level control by feedbac

Strany 10 - BASIC SAFETY INSTRUCTIONS3

18Technical Data6. TECHNICAL DATAOperating Conditions6.1. DANGER!Danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)

Strany 11 - Control Head Type 8681

19Technical DataMechanical data6.3. Cover safeguard:- Seal max Ø2 and / or- plastic self-cutting screw 3.0x10M16x1.5 (2x)G1/4 (2x)G1/8 (3x)Dimension

Strany 12 - GENERAL INFORMATION4

We reserve the right to make technical changes without notice.Technische Änderungen vorbehalten.Sous resérve de modification techniques.© 2010 - 2011 B

Strany 13 - SYSTEM DESCRIPTION5

20Technical Data6.4. Pneumatic DataControl medium: oil-free and dry air, neutral gases Quality classes in accordance with DIN ISO 8573-1 (5 µ

Strany 14 - System Description

21Technical Data6.5. Position Measuring System DataStroke range (measuring range): 0 ... 80 mm Resolution: ≤ 0.1 mm Total fault:

Strany 15 - 5.4.2. Fluid diagram

22Technical Data6.6. Factory Settings in the FirmwareThe control head is supplied with the following factory settings of the firmware: The service int

Strany 16 - Manual Control5.4.5

23Installation7. INSTALLATIONSafety instructions7.1. DANGER!Risk of injury from high pressure in the equipment!Before loosening pneumatic lines and v

Strany 17 - Other Features 5.4.7

24Installationscrews M5), which engage in the middle groove of the hub flange (protection against pulling off). The control head can radially slide int

Strany 18 - 6. TECHNICAL DATA

25InstallationCheck the secure fit of the sealing rings (in the upper and lower grooves). →Mount the control head on the hub flange (seamlessly 360° rot

Strany 19 - Mechanical data6.3

26Opening and Closing the Housing8. OPENING AND CLOSING THE HOUSINGSafety instructions8.1. DANGER!Risk of injury from high pressure in the equipment!

Strany 20 - 6.4. Pneumatic Data

27Opening and Closing the HousingClosing the Housing8.2.2. If necessary, clean the seal contour of the seal and of the hood, and lightly lubricate it

Strany 21 - Technical Data

28Pneumatic Installation9. PNEUMATIC INSTALLATIONSafety instructions9.1. DANGER!Risk of injury from high pressure in the equipment!Before loosening p

Strany 22

29Pneumatic InstallationProcedure:If necessary, realign the control head (see chapter → 7.2.3. Realignment of the Control Head)A silencer has alread

Strany 23 - 7. INSTALLATION

3 Control Head Type 8681In h a l t1. OPERATING INSTRUCTIONS ...

Strany 24 - Installation

30Pneumatic InstallationSettings of the Flow-Rate or the Control Speed with the Help of the Flow Restriction Screws:Open the housing observing the not

Strany 25

3124 V DC - Design10. 24 V DC - DESIGNElectrical connection options 10.1. The following connection concepts are available for the electrical connecti

Strany 26 - Safety instructions8.1

3224 V DC - DesignSolenoid valves: Power input per solenoid valve: max. 0.8 W (0.9 W during activation) Power consumption per solenoid valv

Strany 27 - Closing the Housing8.2.2

3324 V DC - DesignDesign Aid10.3. Power consumption of the electronics:PEl= 0.7 W or IEl= 30 mA at 24 VPower consumption of a valve durin

Strany 28 - 9. PNEUMATIC INSTALLATION

3424 V DC - DesignSafety instructions10.4. DANGER!Danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)!Opening the hoo

Strany 29 - Pneumatic Installation

3524 V DC - DesignNOTE! Use of the Control Head in Explosive AtmosphereOnly use cables and cable glands that are allowed for the respective applicatio

Strany 30

3624 V DC - DesignCircuit diagram 24 V DC: *) Order variant "Analog": output - analog signalCircuit diagram 24 V D

Strany 31 - 10. 24 V DC - DESIGN

3724 V DC - DesignMulti-pole Connection10.5.2. Internal cabling work is not required for models with multi-pole connection, which makes installation a

Strany 32 - 24 V DC - Design

38AS Interface - Design11. AS INTERFACE - DESIGNDefinition11.1. AS Interface ConnectionAS interface (Actuator Sensor Interface) is a field bus system w

Strany 33 - Design Aid10.3

39AS Interface - DesignElectrical Connection Options for AS Interface 11.2. The following connection concepts are available for the electrical connect

Strany 35

40AS Interface - DesignTable of calculated line length of the control head versions:When designing the system, consider the length of the round cable

Strany 36 - Circuit diagram 24 V DC:

41AS Interface - DesignConnections: Multi-pole connection version 1 x M16 x 1.5 cable gland / A/F19 with multi-pole connection (M12 plug a

Strany 37 - Multi-pole Connection10.5.2

42AS Interface - DesignNOTE! If all three solenoid valves are simultaneously controlled via the AS interface, the electronics will activate the valves

Strany 38 - 11. AS INTERFACE - DESIGN

43AS Interface - DesignCalculation Examples:Example 1: 3 valves are activated simultaneously, one position is reported (state for 200 ms):PSlave

Strany 39 - AS Interface - Design

44AS Interface - Design11.7. Electrical installation AS InterfaceInternal cabling work is not required for any of the AS Interface designs with multi

Strany 40 - Electrical Data11.4

45AS Interface - DesignThe cable with multi-pole connection version is especially suited for direct and flexible connection to the AS interface cable h

Strany 41

46AS Interface - Design11.8. Programming DataThe control heads have been configured as AS interface version with an extended address range (A/B slaves

Strany 42 - Design Aid11.5

47DeviceNet - Design12. DEVICENET - DESIGNDefinition12.1. The DeviceNet is a field bus system which is based on the CAN protocol (Controller Area Netwo

Strany 43 - Safety instructions11.6

48DeviceNet - DesignInputs 3 discrete feedback signal of the position measuring system (positions S1 - S3) 1 discrete feedback signal of th

Strany 44

49DeviceNet - DesignElectrical Data12.4. Connections: "Multi-pole" 1 x M16 x 1.5 cable gland / SW22 with multi-pole connection

Strany 45

5 11.5. Design Aid ...

Strany 46 - 11.8. Programming Data

50DeviceNet - DesignDesign Aid12.6. Power consumption of the electronics:PEl= 1.44 W or IEl= 60 mA at 24 VPower consumption of a valve du

Strany 47 - 12. DEVICENET - DESIGN

51DeviceNet - DesignSafety instructions12.7. DANGER!Danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)!Opening the h

Strany 48 - Drop Line Length12.3.2

52DeviceNet - DesignDeviceNet electronics module:Solenoid valve connection with status LED for Valve 1DIP switches for setting the address and baud r

Strany 49 - Electrical Data12.4

53DeviceNet - DesignNetwork Topology of a DeviceNet System12.9. When installing a DeviceNet system, ensure that the terminating circuit of the data li

Strany 50 - Design Aid12.6

54DeviceNet - DesignSettings of the DeviceNet address12.10.1. MAC ID address = Medium Access Control Identifier AddressMAC ID address = [DIP 1 ⋅ 20

Strany 51 - Safety instructions12.7

55DeviceNet - DesignSetting the baud rate12.10.2. Adjustment of the control head to the baud rate of the network.Baud rate DIP 7 DIP 8125 kbaud off of

Strany 52

56DeviceNet - DesignThe addresses listed in the table above ("Static input assemblies") can be used as a path data for the attribute Produce

Strany 53 - Network topologyFig. 21:

57DeviceNet - DesignConfiguration example 12.12.2. The example describes the principle procedure when configuring the device using the software RSNetWor

Strany 54

58DeviceNet - DesignOnline Parameterization of the DeviceDevices can also be parameterized online. In doing so, you can also select whether only indiv

Strany 55

59DeviceNet - DesignState of bus status LED "Network"12.13.2. LED Device state Explanation TroubleshootingOff No voltage / not onlineDevice

Strany 56 - Bus Error

6 13.3. Design Aid ...

Strany 57

60120 V AC - Design 13. 120 V AC - DESIGN Electrical connection options 13.1. Cable gland:Connection left: Voltage, signalsConnection right: ext

Strany 58

61120 V AC - Design Feedback signal output: S4 out is directly connected to S4 inInput / proximity switches (external initiator: S4 in):

Strany 59

62120 V AC - Design Design Aid13.3. Power consumption of the electronics:PEl= 1.2 VA or IEl= 10 mA at 120 VAPower consumption of a valve

Strany 60 - 13. 120 V AC - DESIGN

63120 V AC - Design Safety instructions13.4. DANGER!Risk of injury due to electrical shock (110 ... 130 V AC)!Before reaching into the system (except

Strany 61 - 120 V AC - Design

64120 V AC - Design DANGER!Risk of electric shock if the PE connection is not connected!the PE connection must be connected!•Clamp the protective con

Strany 62 - Design Aid13.3

65120 V AC - Design Designation Terminal stripConfigurationDesignation Terminal stripConfiguration for external initiatorPEProtection earth - protective

Strany 63 - Safety instructions13.4

66Connection of an External InitiatorCONNECTION OF AN EXTERNAL INITIATOR14. DANGER!Danger of explosion in explosive atmosphere (only in the event of a

Strany 64

67Position Measuring System15. POSITION MEASURING SYSTEMThe switching positions of the process valve are reported to the higher-level control by feed

Strany 65

68Position Measuring SystemIf necessary, return control head and system to normal state (switching position, power supply). →Close the housing observi

Strany 66

69Position Measuring SystemAutotune functions15.2.2. Teach-In buttonMode Activa-tion durationopt. feed-backTeach-In buttonFunction Activation duratio

Strany 68 - Teach-In Functions15.2

70Position Measuring System - Then position S2 is taught. - After that, valve V1 is deactivated. It initiates closing of the process valve. - Onc

Strany 69 - Autotune sequence 15.2.3

71Position Measuring SystemAutotune 4:Control Effect on the process valve internal program ErrorT2 + T3 Autotune mode startsT1 + T2Autotune 4 startsVa

Strany 70

72LED - Color Assignments16. LED - COLOR ASSIGNMENTSThe switching states of the feedback positions are signaled centrally to the outside by super-bri

Strany 71 - Reserved function

73LED - Color AssignmentsSetting the Color Combinations16.1. Setting of the possible color combinations with the help of the DIP switches:S1 S2 S3 S4

Strany 72 - 16. LED - COLOR ASSIGNMENTS

74LED - Color AssignmentsBlinking patterns ON OFF Note 250 ms 250 msPermanent blinking in the fault color: - Teaching does not occur

Strany 73 - LED - Color Assignments

75Service Mode / Manual Control 17. SERVICE MODE / MANUAL CONTROL By default, the control head provides the following (e.g. for service purposes):a m

Strany 74 - 16.3. Signal Priorities

76Service Mode / Manual Control Procedure for activating & deactivating the manual control for valve location 2/A1:Observe safety guidelines for t

Strany 75

77Maintenance, TroubleshootingMAINTENANCE, TROUBLESHOOTING18. Safety instructions18.1. DANGER!Risk of injury from high pressure in the equipment!Befor

Strany 76

78Maintenance, Troubleshooting18.2. Safety PositionsSafety positions after failure of the electrical or pneumatic auxiliary power:Operating mode Proc

Strany 77 - Safety instructions18.1

79Maintenance, Troubleshooting18.3. MaintenanceWhen used properly, the Control Head Type 8681 operates maintenance and trouble-free.For service work,

Strany 78 - 18.2. Safety Positions

8Operating InstructionsOPERATING INSTRUCTIONS1. The operating instructions describe the entire life cycle of the device. Keep these instructions in a

Strany 79 - Malfunctions18.5

80Maintenance, TroubleshootingFault description Possible cause of the fault TroubleshootingFeedback signal is lost in system operationPosition in the

Strany 80 - Maintenance, Troubleshooting

81Replacement of Components and ModulesREPLACEMENT OF COMPONENTS AND 19. MODULESIf components or modules need to be replaced for maintenance or servic

Strany 81 - Safety instructions19.1

82Replacement of Components and Modules19.2. Changing the Electronics ModuleNOTE! Electrostatic sensitive components / modules!The device contains el

Strany 82

83Replacement of Components and ModulesInstallation procedure:Carefully insert the entire electronics module into the recess in the lower housing part

Strany 83 - Changing the Valves19.3

84Replacement of Components and ModulesLoosen the electrical connections. →Loosen the connecting screws (Torx T10) for the corresponding valve module.

Strany 84

85Replacement of Components and ModulesDANGER!Risk of injury from high pressure! Before loosening pneumatic lines and valves, turn off the pressure an

Strany 85

86Replacement of Components and ModulesLoosen the electronics module's fastening screw (Torx 10) (see chapter → 19.2. Changing the Electronics

Strany 86

87Spare Parts20. SPARE PARTSCAUTION!Risk of injury and/or damage by the use of incorrect parts!Incorrect accessories and unsuitable spare parts may c

Strany 87 - 20. SPARE PARTS

88ShutdownSHUTDOWN21. Safety instructions21.1. DANGER!Risk of injury from high pressure! Before loosening pneumatic lines and valves, turn off the pre

Strany 88 - SHUTDOWN21

89Packaging and TransportPACKAGING AND TRANSPORT22. NOTE! Transport damage!Inadequately protected equipment may be damaged during transport.During tra

Strany 89 - DISPOSAL24

9Authorized useAUTHORIZED USE2. Non-authorized use of the Control Head Type 8681 may be a hazard to people, nearby equipment and the environment. The